Combustible Dusts and Safety Measures

Managing dust hazards is crucial for maintaining a safe working environment, particularly in industries where dust accumulation can present severe risks. Dust can lead to dangerous situations, including fire and primary and secondary explosions, making it essential to implement effective safety measures. Proper classification of dust-prone areas, adherence to guidelines, and the use of specialized equipment are key to mitigating these risks. This blog post will provide insights into essential safety protocols and strategies for managing dust hazards, focusing on classifications, legal requirements, and best practices to ensure a secure and compliant workplace.

In this blog post, we will thoroughly examine various aspects of dust hazards and safety measures. Here’s what you’ll discover in this article:

Why Classify for Dust?

First, let’s understand why it’s necessary to classify an area containing combustible dust and the various conditions that can trigger a combustible dust explosion. Combustible dusts can explode when in the form of a cloud. For this to occur all five elements of the explosion pentagon must be present: fuel (dust), oxygen, confinement, dispersion, and an ignition source. This behavior is similar to gases and vapors, making it a common hazard in many industrial processes.

Electrical equipment can produce sparks and arcs during normal operation or  during malfunctions, and these can ignite airborne dust clouds, leading to explosions and flash fires. Additionally, the surfaces of electrical equipment can become hot during operation. High surface temperatures can ignite dust clouds in the air as well as dust layers that have settled on equipment surfaces, posing a significant risk of fire or explosion.

Given that approximately 70% of all dusts handled in industry are flammable, the importance of proper area classification and implementation of safety measures cannot be overstated. This high prevalence of flammable dusts underscores the need for meticulous attention to safety protocols to prevent potentially catastrophic dust explosions or fires in industrial settings.

combustible-dust-industry

Dust Cloud Explosion Conditions

Combustible dust explosions are complex events that require the alignment of several critical factors. While sharing similarities with the conventional fire triangle, the Dust Explosion Pentagon introduces additional elements that elevate the risk in industrial settings. When all five elements converge, the risk of a combustible dust explosion increases. This pentagonal interplay distinguishes dust explosions from conventional fires, making them particularly hazardous in industrial settings.

The Five Elements of the Dust Explosion Pentagon

  1. Fuel: Combustible dust particles from materials like wood, metal, or agricultural products serve as the primary fuel source. Unlike typical fires, these particles must be airborne to create an explosive atmosphere.

  2. Oxidant: Oxygen, usually present in the air, acts as the oxidant. When mixed with suspended dust particles, it creates an environment ripe for rapid combustion.

  3. Ignition Source: A spark, flame, hot surface, or electrical arc can provide the energy needed to trigger the combustion reaction.

  4. Confinement: Enclosed spaces like equipment housings or ductwork can trap dust and heat, creating dust concentrations above the Minimum Explosion Concentration (MEC) and temperatures above the Minimum Ignition Temperature (MIT).

  5. Dispersion: When dust particles are widely dispersed in the air, their increased surface area dramatically accelerates the combustion process, leading to more violent explosions.z

Secondary explosions present additional risks

Secondary explosions in industrial settings represent a critical concern due to their potential for devastating consequences. These secondary explosions occur when the initial blast disturbs accumulated dust. The force of the primary explosion can disperse settled dust particles into the air, where they can ignite from residual heat or sparks, triggering a chain reaction of explosions. This phenomenon underscores the importance of rigorous dust control measures, including frequent cleaning to minimize dust accumulation and robust local ventilation systems to remove airborne particles. Proactive safety protocols, including “keeping it in the pipe” and housekeeping are essential to reduce the likelihood of secondary explosions, ensuring the safety of personnel and the integrity of industrial facilities.

Dust Groups – National Electric Code (NEC) Definition

NEC categorizes combustible dusts into specific groups based on their properties and potential hazards. When assessing a facility, identifying the type of material handled and its corresponding NEC group is paramount for implementing appropriate safety measures. NEC defines three main groups of combustible dusts, each with distinct characteristics and associated hazards:

  • Group E: Atmospheres containing combustible metal dusts, such as aluminum, magnesium, and their alloys, or other combustible dusts with similar particle size, abrasiveness, and conductivity characteristics posing risks to electrical equipment.

  • Group F: Atmospheres containing combustible carbonaceous dusts that contain more than 8 percent total entrapped volatiles or have been sensitized by other materials, presenting explosion hazards. Examples include coal, carbon black, charcoal, and coke dusts.

  • Group G: Atmospheres containing combustible dusts not classified under Group E or F, including flour, grain, wood flour, plastic, and chemicals.


Understanding each group’s classification is crucial for determining the appropriate electrical equipment and safety protocols necessary to mitigate risks associated with combustible dusts in industrial settings. This knowledge is essential for ensuring compliance with safety standards and safeguarding personnel and facilities from potential dust-related hazards.

Hazardous Electrical Area Classification

A Hazardous (Electrical) Area Classification (HAC) aims to proactively assess and manage risks associated with electrical equipment in environments where potential hazards exist. There are two classification systems, one is predominantly used in North America, the other is predominantly used in Europe.

European Classifications:

• Zones 0, 1, and 2 are designated for gases and vapors
• Zones 20, 21, and 22 are designated for dust

North American Classifications:

• Class 1, Divisions 1 & 2 are used for gases and vapors
• Class 2, Divisions 1 & 2 are used for combustible dusts

Understanding these classifications and divisions is crucial for ensuring the proper implementation of safety measures in various industrial and hazardous environments.

#Hazardous Electrical Area Classification

Unclassified Area Dust Areas

An Unclassified Area refers to locations that are unlikely to have uncontrolled concentrations of combustible materials. These areas include:

  • Storage of Materials: Areas where materials are stored in sealed containers such as bags, drums, fiber packs on pallets, or racks, ensuring containment and minimal dust emission.

  • Transportation Systems: Areas where materials are transported through well-maintained closed piping systems, preventing the release of dust into the environment.

  • Handling of Palletized Materials: Areas where palletized materials with minimal dust generation are handled or used, maintaining cleanliness and reducing airborne dust.

  • Use of Closed Tanks: Areas where closed tanks are utilized for the storage and handling of materials, ensuring containment and minimizing the potential for dust release.
  • Dust Removal Systems: Implementation of effective dust removal systems to prevent:
    • (a) Formation of visual dust clouds.
    • (b) Accumulation of dust layers that obscure surface colors.

  • Housekeeping Practices: Maintenance of excellent housekeeping practices to prevent:
    • (1) Formation of visual dust clouds.
    • (2) Accumulation of dust layers that make surface colors indiscernible.

Note that dust removal systems installed to maintain an area as unclassified must include adequate safeguards and warnings to mitigate the risk of failure and ensure ongoing effectiveness in dust control.

Housekeeping Guidelines For Dust- NFPA 499 Annex

Housekeeping guidelines according to NFPA 499 Annex recommend classifying areas based on dust accumulation levels. According to these guidelines, areas are classified as follows: Division One when the dust layer thickness exceeds 3.0 mm (1/8 inch), Division Two when the dust layer thickness ranges between 1/8 inch and 3.0 mm (1/8 inch), and Unclassified when surface colors remain discernible under the dust layer. These classifications are essential for implementing appropriate safety measures and maintenance protocols to effectively mitigate the risks associated with combustible dust in industrial environments. 

Installation Techniques :

These specific types of enclosures ensure that equipment inside is safeguarded against environmental elements as per the classification requirements, ensuring safety and compliance in hazardous environments. When installing equipment for Class II, Division 1 and 2 areas according to NEC guidelines, it’s crucial to use appropriate enclosures:

  • NEMA 9 Enclosures: Designed for indoor use in hazardous (classified) locations classified as Class II, Division 1, Groups E, F, or G.
#NEMA 1

NEMA Enclosure Types (from NEMA EN P1-2021)

  • NEMA 4, NEMA 4X, NEMA 12 Enclosures (Division 2): These enclosures can be used indoors or outdoors and provide protection against ingress of solid foreign objects such as falling dirt, windblown dust, circulating dust, lint, fibers, and flyings.
#NEMA2

NEMA Enclosure Types (from NEMA EN P1-2021)

Temperature Class of Electrical Equipment

It’s important to know the ignition temperatures of the materials you are handling. For example, if you have a dust cloud with an ignition temperature of 300°C, you should select equipment classified as T2. This type of equipment is designed to handle such ignition temperatures safely.

Furthermore, we need to consider the layer Ignition temperature (LIT), which is based on the surface temperature of the material. We can determine all these ignition temperatures through various tests. Based on the results of these tests, whether for layers or clouds, we can recommend the appropriate equipment for your facility.

#Temperature Class of Electrical Equipment

Using Local Ventilation as a Mitigation for Dusts:

  • Inadequate local ventilation can lead to larger or stricter area designations for hazardous locations.

  • High local ventilation rates can sometimes downgrade the classification of an area to “unclassified” when the area is of negligible extent.

  • Such high local ventilation rates are typically achieved through local mechanical ventilation systems.

  • Availability of ventilation is crucial for maintaining safe conditions in hazardous areas.

Types of Protection: Intrinsically Safe

Equipment designed for hazardous areas with intrinsically safe barriers includes:

  • 4 to 20 mA DC Instruments
  • Two Wire Transmitters
  • Thermocouples
  • Resistance Thermometer Detector (RTD)
  • Strain Gauges
  • Pressure, Flow, & Level Switches
  • I/P Converters
  • Proximity Switches
  • Infrared Temperature Sensors
  • Potentiometers
  • LED Indicating Lights
  • Magnetic Pickup
  • Flowmeters

Effectively managing dust hazards is essential for ensuring a safe and compliant working environment. By understanding the specific risks associated with dust, implementing appropriate safety measures, and adhering to regulatory guidelines, organizations can significantly reduce the potential for accidents and explosions. Key considerations include classifying dust hazards, recognizing conditions for dust cloud explosions, addressing secondary explosion risks, and following NEC definitions and classifications. Proper housekeeping, installation techniques, temperature management of electrical equipment, and ventilation are also crucial. By employing intrinsically safe protection types and selecting appropriate electrical apparatus for Class II areas, you can create a safer, more secure workplace.